| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Directory traversal vulnerability in miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to read arbitrary files via a ..%5c (dot dot backslash) in a URI. |
| miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle URIs beginning with a 0xfa character, which allows remote attackers to read data from arbitrary memory locations or cause a denial of service (application crash) via a crafted POST request. |
| Multiple directory traversal vulnerabilities in Siemens WinCC 7.0 SP3 before Update 2 allow remote authenticated users to read arbitrary files via a crafted parameter in a URL. |
| Cross-site request forgery (CSRF) vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to hijack the authentication of arbitrary users for requests that modify data or cause a denial of service. |
| WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, stores sensitive information under the web root with insufficient access control, which allows remote attackers to read a (1) log file or (2) configuration file via a direct request. |
| SQL injection vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to execute arbitrary SQL commands via a crafted SOAP message. |
| WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to discover a username and password via crafted parameters to unspecified methods in ActiveX controls. |
| Buffer overflow in the DiagAgent web server in Siemens WinCC 7.0 SP3 through Update 2 allows remote attackers to cause a denial of service (agent outage) via crafted input. |
| Open redirect vulnerability in an unspecified web application in Siemens WinCC 7.0 SP3 before Update 2 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks via a URL in a GET request. |
| Multiple cross-site scripting (XSS) vulnerabilities in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allow remote attackers to inject arbitrary web script or HTML via a (1) GET parameter, (2) POST parameter, or (3) Referer HTTP header. |
| A vulnerability has been identified in SIMATIC WinCC (All versions < V7.5.2.13). Affected applications fail to set proper access rights for their installation folder if a non-default installation path was chosen during installation.
This could allow an authenticated local attacker to inject arbitrary code and escalate privileges. |
| A vulnerability has been identified in Cerberus DMS (All versions), Desigo CC (All versions), Desigo CC Compact (All versions), SIMATIC WinCC OA V3.16 (All versions in default configuration), SIMATIC WinCC OA V3.17 (All versions in non-default configuration), SIMATIC WinCC OA V3.18 (All versions in non-default configuration). Affected applications use client-side only authentication, when neither server-side authentication (SSA) nor Kerberos authentication is enabled. In this configuration, attackers could impersonate other users or exploit the client-server protocol without being authenticated. |